What Goes Where: Battery Storage System Kit
In our new 4 part video series, James takes you through what labels go where on your solar installs.
The Battery Storage System Kit
The Inverter
- The Shutdown Procedure Label- Located adjacent to the PCE to which the battery is connected and be visible from the equipment to be operated
- The Shutdown Procedure Warning Label- Located directly below the shutdown procedure
- Warning Multiple Energy Sources- Located adjacent to the inverter where multiple energy sources are connected
The Switchboard
- ES Label- Located on or adjacent to the main metering panel and main switchboard, so as to be readily visible.
- Warning Multiple Mode IES- Located on or adjacent to the main metering panel and main switchboard, so as to be readily visible.
- Main Switch Stand Alone Supply- Located in the main switchboard for the stand alone circuit
The Battery Enclosure
- Battery System Voltage Labels- White; Located adjacent to enclosure where the battery system is located, for systems below DVC-A. Red is for systems over DVC-A
- Danger Risk of Battery Explosion- Located adjacent to enclosure where the battery system is located
- Danger Toxic Fumes- Located adjacent to enclosure where the battery system is located
- Warning Arc Flash Hazard- Located adjacent to enclosure where the battery system is located
- Battery System Isolator- Located on the battery system isolation device
As per Australian Standards 139:2019 & AS4777.1:2016, it is essential that you put your labels in the correct place to pass inspection. Get in touch with the team if you have any questions- sales@pvconnections.com.au; 1300 818 419.
Watch the rest of our videos in the series- What Goes Where