What Goes Where: Battery Storage System Kit

In our new 4 part video series, James takes you through what labels go where on your solar installs.

 

The Battery Storage System Kit

The Inverter

  • The Shutdown Procedure Label- Located adjacent to the PCE to which the battery is connected and be visible from the equipment to be operated
  • The Shutdown Procedure Warning Label- Located directly below the shutdown procedure
  • Warning Multiple Energy Sources- Located adjacent to the inverter where multiple energy sources are connected

The Switchboard

  • ES Label- Located on or adjacent to the main metering panel and main switchboard, so as to be readily visible.
  • Warning Multiple Mode IES- Located on or adjacent to the main metering panel and main switchboard, so as to be readily visible.
  • Main Switch Stand Alone Supply- Located in the main switchboard for the stand alone circuit

The Battery Enclosure

  • Battery System Voltage Labels- White; Located adjacent to enclosure where the battery system is located, for systems below DVC-A. Red is for systems over DVC-A
  • Danger Risk of Battery Explosion- Located adjacent to enclosure where the battery system is located
  • Danger Toxic Fumes- Located adjacent to enclosure where the battery system is located
  • Warning Arc Flash Hazard- Located adjacent to enclosure where the battery system is located
  • Battery System Isolator- Located on the battery system isolation device
  •  